| Technical
Data |
|
Working voltage
|
Upto
1100 V
|
|
Temperature range
|
-15 deg C to +70 deg C
|
|
Sizes
|
Available
in 1.0, 1.5, 2.5, 4.0 and 6.0 sq mm
|
| Color
codes
|
Red, Yellow, Blue, Black and Green (for earthing)
|
| Specification
|
IS 694:1990
|
| Approvals
|
FIA/TAC,
ISI marked
|
| Packing
|
In 90-meter coils in attractive cartons
|
|
Nominal area of Conductor
|
Number/Nom. Dia. of Wire
|
Thickness of Insulation (Nom.)
|
Approx. Overall Dia.
|
Current carrying capacity *
2 cables, single phase
|
Current carrying capacity *
2 cables, single phase
|
Resistance (Max) per Km.@20°C
|
|
Sq.
mm
|
mm
|
mm
|
mm
|
Amps.
|
Amps.
|
Ohms.
|
|
1.0
|
14/.3
|
0.7
|
2.8
|
11
|
12
|
18.10
|
|
1.5
|
22/.3
|
0.7
|
3.1
|
13
|
16
|
12.10
|
|
2.5
|
36/.3
|
0.8
|
3.8
|
18
|
22
|
7.41
|
|
4.0
|
56/.3
|
0.8
|
4.4
|
24
|
29
|
4.95
|
|
6.0
|
84/.3
|
0.8
|
5.0
|
31
|
37
|
3.30
|
*
As per IS 3961 (Part V) - 1968.
Standard Colors : Black, Red, Blue, Yellow, and Green (For earthing).
Supplied in 90 metre lengths in attractive cartons.
Conform to IS 694:1990. BIS Lincence no. CM/L - 0382242 and CM/L
- 7306463 |
|
Nominal area of Conductor
|
Number/Nom. Dia. of Wire
|
Thickness of Insulation (Nom.)
|
Approx. Overall Dia.
|
Current carrying capacity *
2 cables, single phase
|
Current carrying capacity *
2 cables, single phase
|
Resistance (Max) per Km.@20°C
|
|
Sq.
mm
|
mm
|
mm
|
mm
|
Amps.
|
Amps.
|
Ohms.
|
|
10
|
80/.4
OR 140/.3
|
1.0
|
6.6
|
42
|
51
|
1.91
|
|
16
|
126/.4
|
1.0
|
7.8
|
57
|
68
|
1.21
|
|
25
|
196/.4
|
1.2
|
9.7
|
71
|
86
|
0.780
|
|
35
|
276/.4
|
1.2
|
10.9
|
91
|
110
|
0.554
|
|
50
|
396/.4
|
1.4
|
13.2
|
120
|
145
|
0.386
|
Standard Colors : Black, Red, Blue, and Yellow. Other colours
on request.
Supplied in 100 metre lengths in coils.
Conform to IS 694:1990. BIS Lincence no. CM/L - 0382242 and CM/L
- 7306463 |
Top
|
|